Motor starting disturbance

Motor Starting Voltage Dip Estimator — Model the Starting Sag

Estimate the first-pass voltage dip when a motor starts by comparing starting current with the source short-circuit current. Use the result to identify scenarios that deserve a more detailed system study.

Starting and source inputs

V line-to-line
A
MVA
% dip comparison level
This is a simplified impedance-based estimator. Actual voltage dip can depend on source impedance, transformer impedance, feeder impedance, motor power factor, starter method and other system characteristics.
Enter the source and motor starting values.

How the simplified voltage-dip estimate works

For a three-phase source, short-circuit current can be approximated from short-circuit MVA and system voltage. A simplified voltage-dip ratio can then be estimated from motor starting current divided by source short-circuit current.

Why source strength matters

A strong source has a large short-circuit capacity and therefore a larger short-circuit current. The same motor can create a smaller percentage voltage dip on a stronger source than on a weaker one.

What the review level means

The review level is your own screening threshold. It is not presented as a universal limit because acceptable voltage variation depends on the system and equipment.

Worked example

At 400 V, a 20 MVA source has an approximate short-circuit current of 28.9 kA. A 150 A motor starting current would therefore produce a simplified voltage-dip estimate of about 0.52% before feeder and transformer effects are separately considered.

Where this model becomes insufficient

For a final assessment, the impedance of the transformer, feeder, connection point and starting method may need to be modeled explicitly rather than collapsed into a single source MVA value.

Frequently asked questions

Does this calculate actual measured voltage sag?

No. It is an electrical source-strength estimate.

Can soft starters or variable-frequency drives change the result?

Yes. A lower starting current changes the estimated dip substantially.

Why is short-circuit MVA used?

It provides a convenient way to represent source strength without requiring a detailed impedance network.

Is the review level a code requirement?

No. It is a screening value selected by the user.

Related Electricity & Solar Tools

Motor Starting kVA CalculatorEstimate the apparent power demanded during motor starting. Electrical Equipment Simultaneous-Use AnalyzerCompare grouped operating demand across equipment combinations. Electrical Service Upgrade Impact AnalyzerCheck how proposed demand changes an existing service scenario. More Electricity & Solar ToolsBrowse the main electricity planning hub.